Model-matched test evidence
What does type-test report Dz2023201944 support?
Identity and scope
Shenyang Fire Research Institute, Ministry of Emergency Management issued a type test report (not a product certification certificate) for model WANLIN-340. The report lists 14 samples and a test period of 2023-09-26 to 2023-12-04.
Test basis and conclusion
The stated basis is GB 30122-2013 and GB 12978-2003 inspection rules. The report concludes: All applicable GB 30122-2013 items tested in the report were judged compliant.
Measured results
Two action-temperature results shown are 58.5 °C and 58.3 °C. Initial sound-pressure results for 14 samples range from 70.5 to 72.5 dB. These are report measurements, not guaranteed values for every production unit.
Evidence boundary: the report is dated 2023-12-07 and identifies a Class AS, point-type fixed-temperature alarm. It does not by itself prove that every radio or cloud variant has identical construction, nor does it constitute destination-market approval.